11kv Staywire Insulator
OLF Reference | 39EH08 | |||
Dimensions | Overall width Overall length Diameter of hole Total creepage distance – Minimum |
mm mm mm mm |
75 120 21 70 |
|
Min Failing Load | Mechanical Test | kN | 110 | |
Electrical characteristics | Power frequency flashover Voltage Impulse withstand voltage |
Wet | kV (rms)
kV (pk) |
17
50 |
Weight | Weight of unit | kg | 1.2 |
The electrical characteristics have been obtained from tests carried out in accordance with BS EN 60383-1
20kv Staywire Insulator - Porcelain
OLF Reference | 39EH11 | |||
Dimensions | Overall width Overall length Diameter of hole Total creepage distance – Minimum |
mm mm mm mm |
100 210 22 110 |
|
Min Failing Load | Mechanical Test | kN | 70 | |
Electrical characteristics | Power frequency flashover Voltage Power frequency withstand |
Dry Wet Dry |
kV (rms) kV (rms) kV (rms) |
26 25 25 |
Weight | Weight of unit | kg | 2.6 |
The electrical characteristics have been obtained from tests carried out in accordance with BS EN 60383-1
33kV Staywire Insulator - Porcelain
OLF Reference | 39EH09 | |||
Dimensions | Overall width Overall length Diameter of hole Total creepage distance – Minimum |
mm mm mm mm |
120 220 28 95 |
|
Min Failing Load | Mechanical Test | kN | 140 | |
Electrical characteristics | Power frequency flashover Voltage – Single unit – 2 units in series Impulse withstand and voltage – Single unit – 2 unit series |
Wet Wet |
kV (rms) kV (rms) kV (pk) kV (pk) |
26 48 75 150 |
Weight | Weight of unit | kg | 5.4 |
The electrical characteristics have been obtained from tests carried out in accordance with BS EN 60383-1