80kN Plain Disc Insulator
OLF Reference | 40EY02 | |||
Dimensions | Diameter Spacing Total creepage distance – Minimum Ball and socket coupling size |
mm mm mm |
254 140 300 16B |
|
Min Failing Load | Electro-megnetical test | kN | 80 | |
Electrical characteristics | Power frequency flashover Voltage Impulse flashover voltage Power frequency withstand |
Dry Wet Positive Negative Dry Wet |
kV (rms) kV (rms) kV (pk) kV (pk) kV (rms) kV (rms) kV (pk) kV (rms) |
80 50 125 130 70 45 100 110 |
Weight | Weight of unit | kg | 5.2 |
The electrical characteristics have been obtained from tests carried out in accordance with BS EN 60383-1
125kN Plain Disc Insulator
OLF Reference | 41EY00 | |||
Dimensions | Diameter Spacing Total creepage distance – Minimum Ball and socket coupling size |
mm mm mm mm |
280 178 340 20 |
|
Min Failing Load | Electro-megnetical test | kN | 125 | |
Electrical characteristics | Power frequency flashover Voltage Impulse flashover voltage Power frequency withstand |
Dry Wet Positive Negative Dry Wet |
kV (rms) kV (rms) kV (pk) kV (pk) kV (rms) kV (rms) kV (pk) kV (rms) |
80 50 125 130 70 45 100 110 |
Weight | Weight of unit | kg | 8.5 |
The electrical characteristics have been obtained from tests carried out in accordance with BS EN 60383-1
80kN Anti-Fog Disc Insulator
OLF Reference | 41EY12 | |||
Dimensions | Diameter Spacing Total creepage distance – Minimum Ball and socket coupling size |
mm mm mm |
254 140 432 16B |
|
Min Failing Load | Electro-megnetical test | kN | 80 | |
Electrical characteristics | Power frequency flashover Voltage Impulse flashover voltagePower frequency withstand Voltage (one minute) Impulse withstand voltage Power frequency Puncture Voltage |
Dry Wet Positive Negative Dry Wet |
kV (rms) kV (rms) kV (pk) kV (pk) kV (rms) kV (rms) kV (pk) kV (rms) |
100 60 150 150 90 50 125 130 |
Weight | Weight of unit | kg | 7.0 |
The electrical characteristics have been obtained from tests carried out in accordance with BS EN 60383-1